Unified inbox — grid operations and electrical-safety alarms

26
Total Alarms
15
Active
4
Critical (open)
4
Resolved
SeverityAlarmSourceLocationTimeStatusActions
Critical
Compressor restart loop — 1h38m abnormal draw
Current draw 78A persisted for 98 minutes on a 63A-rated skid feed. Pattern matches a compressor failing to reach run speed and short-cycling. 7 similar events at this plot in last 60 days.
SAF-2026-0520-001 · Abnormal Load
Safety WatchJurong Island · Singapore2m agoActive
View
Critical
Earth leakage 64mA — switchroom breaker tripped
Sustained earth leakage current 64mA detected on the switchroom main. Tier-1 local breaker tripped within 38ms. Feed isolated pending field check.
SAF-2026-0520-002 · Earth Leakage
Safety WatchTuas · Singapore42m agoAcknowledged
Warning
Recurring undervoltage at shift change
sensor SS-JURONG-ISLAND-011 consistently sees voltage < 198V between 19:00-21:00. Recommend feeder review.
SAF-2026-0520-101 · Undervoltage
Safety WatchJurong Island · Singapore2h agoAcknowledged
Warning
Boiler burner circuit 78°C
Burner circuit terminal heating up at sensor SS-TUAS-005; suggests loose connection.
SAF-2026-0520-108 · Overtemperature
Safety WatchTuas · Singapore2h agoAcknowledged
Warning
Sustained overcurrent — rate-limited
Current draw 92A on an 80A-rated process feed at sensor SS-WOODLANDS-009. Tier-1 rate-limit engaged.
SAF-2026-0520-113 · Overcurrent
Safety WatchWoodlands · Singapore2h agoAcknowledged
Warning
Recurring undervoltage at shift change
sensor SS-CHANGI-BP-012 consistently sees voltage < 198V between 19:00-21:00. Recommend feeder review.
SAF-2026-0520-117 · Undervoltage
Safety WatchChangi Business Park · Singapore2h agoAcknowledged
Critical
Boiler burner circuit 118°C — sustained 6 min
Boiler-room burner & feedwater pump circuit reached 118°C, threshold 80°C. Tier-1 rate-limit engaged. Field unit dispatched.
SAF-2026-0520-003 · Overtemperature
Safety WatchJurong Island · Singapore2h agoAcknowledged
Warning
Likely compressor short-cycle — 40 min
Pattern matches a compressor short-cycling at sensor SS-JURONG-ISLAND-019. Below trip threshold.
SAF-2026-0520-102 · Abnormal Load
Safety WatchJurong Island · Singapore3h agoActive
View
Warning
Overvoltage 244V — 12 min
Brief overvoltage at sensor SS-TUAS-012, likely solar export peak. Within tolerance but logged.
SAF-2026-0520-109 · Overvoltage
Safety WatchTuas · Singapore3h agoActive
View
Warning
Switchgear busbar temperature 72°C
Busbar joint temperature elevated at sensor SS-WOODLANDS-021. Recommend torque check or thermography.
SAF-2026-0520-114 · Overtemperature
Safety WatchWoodlands · Singapore3h agoActive
View
Warning
Likely compressor short-cycle — 40 min
Pattern matches a compressor short-cycling at sensor SS-CHANGI-BP-020. Below trip threshold.
SAF-2026-0520-118 · Abnormal Load
Safety WatchChangi Business Park · Singapore3h agoActive
View
Critical
Arc fault detected — feed isolated
AFCI flagged signature event on a wafer-fab utilities feed. Feed auto-isolated within 42ms. Field crew confirmed degraded insulation in an MCCB; replaced.
SAF-2026-0520-004 · Arc Fault
Safety WatchWoodlands · Singapore3h agoResolved
Critical
Unauthorised tap on metered feed (theft signature)
Off-hour 96A draw on a feed rated 80A. Repeat pattern across 3 nights; voltage drop on the neighbouring monitored plot suggests an illegal tap.
SAF-2026-0520-005 · Abnormal Load
Safety WatchJurong Island · Singapore4h agoAcknowledged
Warning
Sustained overcurrent — rate-limited
Current draw 92A on an 80A-rated process feed at sensor SS-JURONG-ISLAND-024. Tier-1 rate-limit engaged.
SAF-2026-0520-103 · Overcurrent
Safety WatchJurong Island · Singapore4h agoActive
View
Warning
Pump startup spike — 3 cycles in 5 min
Repeated pump startup spikes at sensor SS-TUAS-022 suggest a failing motor.
SAF-2026-0520-110 · Overcurrent
Safety WatchTuas · Singapore4h agoActive
View
Warning
Recurring undervoltage at shift change
sensor SS-WOODLANDS-030 consistently sees voltage < 198V between 19:00-21:00. Recommend feeder review.
SAF-2026-0520-115 · Undervoltage
Safety WatchWoodlands · Singapore4h agoActive
View
Warning
Switchgear busbar temperature 72°C
Busbar joint temperature elevated at sensor SS-JURONG-ISLAND-033. Recommend torque check or thermography.
SAF-2026-0520-104 · Overtemperature
Safety WatchJurong Island · Singapore5h agoActive
View
Warning
Leakage 18mA below trip threshold
Leakage current trending up; 18mA sustained 4 min. Below trip threshold but recommend inspection at sensor SS-TUAS-038.
SAF-2026-0520-111 · Earth Leakage
Safety WatchTuas · Singapore5h agoActive
View
Warning
Likely compressor short-cycle — 40 min
Pattern matches a compressor short-cycling at sensor SS-WOODLANDS-042. Below trip threshold.
SAF-2026-0520-116 · Abnormal Load
Safety WatchWoodlands · Singapore5h agoActive
View
Critical
Process motor 188A — breaker tripped
Process-motor circuit hit 188A (rated 160A). Tier-1 trip engaged. Plant adjusted load sequencing; restored.
SAF-2026-0520-006 · Overcurrent
Safety WatchTuas · Singapore6h agoResolved
Warning
Recurring undervoltage at shift change
sensor SS-JURONG-ISLAND-041 consistently sees voltage < 198V between 19:00-21:00. Recommend feeder review.
SAF-2026-0520-105 · Undervoltage
Safety WatchJurong Island · Singapore6h agoActive
View
Warning
Boiler burner circuit 78°C
Burner circuit terminal heating up at sensor SS-TUAS-047; suggests loose connection.
SAF-2026-0520-112 · Overtemperature
Safety WatchTuas · Singapore6h agoActive
View
Warning
Likely compressor short-cycle — 40 min
Pattern matches a compressor short-cycling at sensor SS-JURONG-ISLAND-058. Below trip threshold.
SAF-2026-0520-106 · Abnormal Load
Safety WatchJurong Island · Singapore7h agoActive
View
Warning
Sustained overcurrent — rate-limited
Current draw 92A on an 80A-rated process feed at sensor SS-JURONG-ISLAND-065. Tier-1 rate-limit engaged.
SAF-2026-0520-107 · Overcurrent
Safety WatchJurong Island · Singapore8h agoActive
View
Info
Mild overvoltage 244V — auto-corrected by CityOG
Voltage 244V (1.061 pu) for 18 min. Auto-resolved when feeder tap-changer kicked in.
SAF-2026-0519-008 · Overvoltage
Safety WatchChangi Business Park · Singapore1d agoResolved
Showing 1–25 of 26 alarms